Please use this identifier to cite or link to this item: https://idr.l2.nitk.ac.in/jspui/handle/123456789/7910
Title: Effects of Thyristor Controlled Series Capacitor (TCSC) on oscillations in tie-line power and area frequencies in an interconnected non-reheat thermal power system
Authors: Abraham, N.M.
Parameswaran, A.P.
Abraham, R.J.
Issue Date: 2011
Citation: 2011 International Conference on Power and Energy Systems, ICPS 2011, 2011, Vol., , pp.-
Abstract: This paper deals with automatic generation control of an interconnected thermal non-reheat power system in continuous mode by employing a Thyristor Controlled Series Capacitor (TCSC) in series with the line. Damping of the system frequency and tie-line power oscillations by controlling the reactance of the TCSC is presented. Gain values of the integral controllers are optimised using the integral squared error method by providing a step load disturbance in each of the areas by minimising a quadratic performance index. It is reported that TCSC can dampen the tie-line and power oscillations commendably under sudden load disturbances in any of the areas. � 2011 IEEE.
URI: http://idr.nitk.ac.in/jspui/handle/123456789/7910
Appears in Collections:2. Conference Papers

Files in This Item:
File Description SizeFormat 
7910.pdf374.53 kBAdobe PDFThumbnail
View/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.