Please use this identifier to cite or link to this item:
https://idr.l2.nitk.ac.in/jspui/handle/123456789/7591
Title: | Current injection based front-end power quality improved converter for telecom load |
Authors: | Saravana, Prakash, P. Kalpana, R. Singh, B. Bhuvaneswari, G. |
Issue Date: | 2017 |
Citation: | 2016 1st International Conference on Sustainable Green Buildings and Communities, SGBC 2016, 2017, Vol., , pp.- |
Abstract: | In this paper a front-end converter having third harmonic current injection technique is used for improving input current shape as near sinusoidal. Here zig-zag transformer is used as the current injection device so that the advantages pertaining to zig-zag transformer is utilized effectively. The third harmonic current injection device along with the three-level boost converter at the output stage will increase the dc-link voltage and the current is injected through zig-zag transformer. The power quality is well improved using third harmonic current modulated front-end structure which is very well applicable to telecom load having the high current low voltage. Extensive simulation is carried out for the 12 kW load and the results are verified through experimental setup. The experimental setup is tested for reduced voltage rating and the test results are presented. � 2016 IEEE. |
URI: | http://idr.nitk.ac.in/jspui/handle/123456789/7591 |
Appears in Collections: | 2. Conference Papers |
Files in This Item:
There are no files associated with this item.